erdemir

436 ve 9055 ile ilgili bilgi arıyorum
aynası iştir kişinin lafa bakılmaz...

siefan

İngilizce alarm açıklamalarını yolluyorum anladığım kadarıyla servo motorda sorun var.


SV0436 Soft thermal (OVC)
3.3.3 Overload Alarm (Soft Thermal, OVC)
(Alarm identification method)
#7 #6 #5 #4 #3 #2 #1 #0
<1> Alarm 1 OVL LVA OVC HCA HVA DCA FBA OFA
(Action)
(1) Make sure that the motor is not vibrating.
_ If a motor vibrates, the current flowing in it becomes more
than necessary, resulting in an alarm.
(2) Make sure that the power lead to the motor is connected correctly.
_ If the connection is incorrect, an abnormal current flows in
the motor, resulting in an alarm.
(3) Make sure that the following parameters are set correctly.
_ An overload alarm is issued based on the result of calculation
of these parameters. Be sure to set them to the standard values.
For details of the standard values, refer to the FANUC AC
SERVO MOTOR αis/αi series Parameter Manual (B-
65270EN).
No. 1877 (FS15i) Overload protection coefficient (OVC1)
No. 2062 (FS16i)
No. 1878 (FS15i) Overload protection coefficient (OVC2)
No. 2063 (FS16i)
No. 1893 (FS15i) Overload protection coefficient (OVCLMT)
No. 2065 (FS16i)
No. 1785 (FS15i) Overload protection coefficient (OVC21)
No. 2162 (FS16i)
No. 1786 (FS15i) Overload protection coefficient (OVC22)
No. 2163 (FS16i)
No. 1787 (FS15i) Overload protection coefficient (OVCLMT2)
No. 2165 (FS16i)
(4) Attach the check board to connector JX5 to measure the
waveform of the actual current (IR and IS) of the servo amplifier
module. (This check pin board differs from that for the α series.)
Run the motor and measure its actual currents (IR and IS). Then
compare the measurement results with the overload duty curve
shown in "FANUC AC SERVO MOTOR αis/αi series
Descriptions (B-65262EN)," and see whether the machine load is
too heavy compared with the motor capacity. If the actual current
is high on acceleration/deceleration, it is likely that the time
constant is too small.



9055 7n55 Abnormal switching status of power leads 3.4.27
3.4.27 Alarm Code 55
In spindle switching control or output switching control, a mismatch
between the switching request signal (SPSL or RSL) and the power
lead state check signal (MCFN, MFNHG, RCH, or RCHHG) continues
during motor activation.
Troubleshooting when this alarm is issued
(a) The magnetic contactor (switch unit) for power lead switching is
faulty.
If the contact is inoperative, check the power supply of the
magnetic contactor. If the magnetic contactor is still inoperative,
replace the magnetic contactor.
(b) The I/O unit or wiring for checking the contact of the magnetic
contactor is faulty.
If a defect is found in the I/O unit or wiring, replace the I/O unit or
wiring.
(c) The sequence (ladder) is incorrect.
Modify the sequence so that switching is not performed during
activation. For details of the signals, refer to "FANUC SERVO
AMPLIFIER αi series Descriptions (B-65282EN)."